Voltage Window Comparators (1-phase or 3-phase)
|
Rhomberg voltage window comparators, are used to monitor AC (1-ph or 3-ph) or DC power supply voltages, and switch a relay contact at a pre-determined level, primarily used for overvoltage and/or undervoltage protection of equipment connected to that power supply. (Available in 11-pin plug-in or DIN rail format)
|
|
 |
AP221
| |
Single Phase Supply Monitoring Relay- Voltage Window Comparator AC/ DC
|
|
Overvoltage and/or Undervoltage monitoring of power supply
|
|

| |
Features
- DIN rail mount.
- Fail-to-safe design.
- Combined overvoltage and undervoltage monitoring.
- Monitoring of own supply voltage (single phase).
- Separately adjustable setpoints: over-voltage, (5 to 20%) and, under-voltage (-5 to -20%).
- Separately adjustable response times on trip & recovery (0.1 to 10 seconds).
- Fixed hysteresis: 2%.
- Adjustable start-up delay for disabling latching 0.1 to 10 sec.
- Selectable latching (ie manual or auto reset).
- LED indication of Relay ON and fault type.
- 5A DPDT relay output.
- Supersedes P220P
|
| |
Data Sheet
More Info
Order Code
|
Search |
Top
|
 |
AP224
| |
Single Phase Supply Monitoring Relay- Voltage Window Comparator AC/ DC
|
|
Overvoltage and/or Undervoltage monitoring of power supply (2 Independent Relay Outputs)
|
|

| |
Features
- DIN rail mount.
- Fail-to-safe design.
- Combined overvoltage and undervoltage monitoring.
- Monitoring of own supply voltage (single phase).
- Separately adjustable setpoints: over-voltage, (5 to 20%) and, under-voltage (-5 to -20%).
- Separately adjustable response times on trip & recovery (0.1 to 10 seconds).
- Fixed hysteresis: 2%.
- Adjustable start-up delay for disabling latching 0.1 to 10 sec.
- Selectable latching (ie manual or auto reset).
- LED indication of Relay ON and fault type.
- 2 x 10A SPDT relay outputs (1 for Overvoltage, 1 for Undervoltage)
|
| |
Data Sheet
More Info
Order Code
|
Search |
Top
|
 |
AP231/AP232
| |
3 Phase Supply Monitoring Relay- Voltage Window Comparator
|
|
Overvoltage and/or Undervoltage monitoring of power supply
|
|

| |
Features
- AP231 monitors 3 Phases only, AP232 monitors 3 Phases and Neutral
- Protection of phase failure & incorrect phase sequence
- DIN rail mount.
- Fail-to-safe design.
- Combined overvoltage and undervoltage monitoring with phase failure or sequence detection
- Monitoring of own supply voltage (3 phase).
- Separately adjustable setpoints: over-voltage, (5 to 20%) and, under-voltage (-5 to -20%).
- Separately adjustable response times on trip & recovery (0.1 to 10 seconds).
- Fixed hysteresis: 2%.
- Adjustable start-up delay for disabling latching 0.1 to 10 sec.
- Selectable latching (ie manual or auto reset).
- LED indication of Relay ON and fault type.
- 10A SPDT relay output.
- AP231 Supersedes P230P.
|
| |
Data Sheet
More Info
Order Code
|
Search |
Top
|
 |
AP234/AP235
| |
3 Phase Supply Monitoring Relay- Voltage Window Comparator
|
|
Overvoltage and/or Undervoltage monitoring of power supply (2 Independent Relay Outputs)
|
|

| |
Features
- AP234 monitors 3 Phases only, AP235 monitors 3 Phases and Neutral
- Protection of phase failure & incorrect phase sequence
- DIN rail mount.
- Fail-to-safe design.
- Combined overvoltage and undervoltage monitoring with phase failure or sequence detection
- Monitoring of own supply voltage (3 phase).
- Separately adjustable setpoints: over-voltage, (5 to 20%) and, under-voltage (-5 to -20%).
- Separately adjustable response times on trip & recovery (0.1 to 10 seconds).
- Fixed hysteresis: 2%.
- Adjustable start-up delay for disabling latching 0.1 to 10 sec.
- Selectable latching (ie manual or auto reset).
- LED indication of Relay ON and fault type.
- 2 x 10A SPDT relay outputs (1 for Overvoltage, 1 for Undervoltage)
|
| |
Data Sheet
More Info
Order Code
|
Search |
Top
|
 |
SP221
| |
Single Phase Supply Monitoring Relay- Voltage Window Comparator AC/ DC
|
|
Overvoltage and/or Undervoltage monitoring of power supply
|
|

| |
Features
- 11-pin plug-in.
- Fail-to-safe design.
- Combined overvoltage and undervoltage monitoring.
- Monitoring of own supply voltage (single phase).
- Separately adjustable setpoints: over-voltage, (5 to 20%) and, under-voltage (-5 to -20%).
- Adjustable response time on trip (0.1 to 10 seconds).
- Fixed hysteresis: 2%.
- Fixed start-up delay for disabling latching 10 sec.
- Selectable latching (ie manual or auto reset).
- LED indication of Relay ON and fault type.
- 10A SPDT relay output.
- Supersedes SP220.
- Requires optional S3-B 11-pin base.
|
| |
Data Sheet
More Info
Order Code
|
Product Comparison |
Search |
Top
|
 |
SP231/SP232
| |
3 Phase Supply Monitoring Relay- Voltage Window Comparator
|
|
Overvoltage and/or Undervoltage monitoring of power supply
|
|

| |
Features
- SP231 monitors 3 Phases only, SP232 monitors 3 Phases and Neutral
- 11-pin plug-in.
- Fail-to-safe design.
- Combined overvoltage and undervoltage monitoring.
- Monitoring of own supply voltage (3 phase).
- Separately adjustable setpoints: over-voltage, (5 to 20%) and, under-voltage (-5 to -20%).
- Adjustable response time on trip (0.1 to 10 seconds).
- Fixed hysteresis: 2%.
- Fixed start-up delay for disabling latching 10 sec.
- Selectable latching (ie manual or auto reset).
- LED indication of Relay ON and fault type.
- 10A SPDT relay output.
- Supersedes SP230.
- Requires optional S3-B 11-pin base.
|
| |
Data Sheet
More Info
Order Code
|
Product Comparison |
Search |
Top
|