Level Control Relays & Conductive Probes
|
Rhomberg level control relays are primarily used in conjunction with conductive level probes (refer to Rhomberg CP-3C level probes) for controlling the level of a liquid between a high and a low level, for filling or draining applications. These units normally control pumps. (Available in 11-pin plug-in or DIN rail format)
|
|
|
AC130
| |
Liquid Level Relay (Single or Dual Level) 1 C/O or 2 C/O
|
|
Filling or Draining control of pumps using conductive probes
|
|
| |
Features
- DIN rail mount.
- Fail-to-safe design.
- Programmable: charging (filling), discharging (draining).
- Adjustable Sensitivity: 0- 100k ohms.
- AC modulation of probe signal to prevent plating and electrolytic corrosion.
- 1 or 2 level control.
- Sensing of conductive liquids.
- Low voltage probe signals for human safety and certain hazardous environments.
- Works with all types of conductive probes (Rhomberg CP-3C, CP-2C or CP-1C probes recommended).
- 10A SPDT or 5A DPDT relay output.
- Power ON & Relay ON LED's.
|
| |
Data Sheet
More Info
Order Code
|
Product Comparison |
Search |
Top
|
|
CP-3C
| |
Conductive Probe Kit - Probe Holders with 3 rods
|
|
Liquid level probes for use with Rhomberg SC130 & AC130 level control relays
|
|
| |
Features
- Probe holder 1.5
- BSP Nylon
- Supplied with 3 x 1m SS316 rods
- Rods and connectors powder coated to ensure reliable switching only between bare ends
- IP65
- Optional 1 metre extension rods Male/Female (part code EP1/CEXT)
- Connectors and spacers available
|
| |
Data Sheet
More Info
|
Product Comparison |
Search |
Top
|
|
DD
| |
Distance Disc for CP-1C, CP-2C, CP-3C
|
|
|
|
| |
Features
- Keeps CP level probes fixed distance apart
- DD1 for CP-1C, DD2 for CP-3C, DD3 for CP3C
|
| |
|
Search |
Top
|
|
SC100
| |
Switching Relay for Resistive Sensors (Single Point Level Control Relay)
|
|
Alarm level detection, detection of rain, moisture, absence of water
|
|
| |
Features
- 11-pin plug-in.
- AC modulation of probe signal to prevent plating and electrolytic corrosion.
- Low voltage probe signal for human safety and certain hazardous environments.
- Adjustable Sensitivity from 15k to 500k Ohms.
- 10A SPDT relay output.
- Requires optional S3-B 11-pin base.
|
| |
Data Sheet
More Info
Order Code
|
Product Comparison |
Search |
Top
|
|
SC130
| |
Liquid Level Relay (Single or Dual Level) 1 C/O or 2 C/O
|
|
Filling or Draining control of pumps using conductive probes
|
|
| |
Features
- 11-pin plug-in.
- Fail-to-safe design.
- Programmable: charging (filling), discharging (draining).
- Adjustable Sensitivity: 0- 50k ohms.
- AC modulation of probe signal to prevent plating and electrolytic corrosion.
- 1 or 2 level control.
- Sensing of conductive liquids.
- Low voltage probe signals for human safety and certain hazardous environments.
- Works with all types of conductive probes (Rhomberg CP-3C, CP-2C or CP-1C probes recommended).
- 10A SPDT or 5A DPDT relay output.
- Relay ON LED.
- Requires optional S3-B 11-pin base.
|
| |
Data Sheet
More Info
Order Code
|
Product Comparison |
Search |
Top
|
|
SC230
| |
Level Control Relay (Single or Dual) for Namur Sensors
|
|
Filling or Draining control using proximity sensors
|
|
| |
Features
- 11-pin plug-in.
- Fail-to-safe design.
- Programmable: charging, discharging, single or dual sensor option.
- Direct interface with Rhomberg & other Namur sensors (DIN 19234).
- Independent indication: sensor status, sensor or cable fault, relay status.
- High speed solid state transistor output.
- Direct interface for solid state relays.
- 10A SPDT relay output.
- Requires optional S3-B 11-pin base.
|
| |
Data Sheet
More Info
Order Code
|
Product Comparison |
Search |
Top
|